DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming C.1 TP Memory Map A-2 Specifications Control Method Stored program, cyclic scan system Batch processing method (when END instruction is executed) I/O Processing Method Execution Speed LD instructions – 0.54µs, MOV instructions – 3.4µs Program language Instruction List + Ladder + SFC Program Capacity TP70P-RM0: 2k, TP70P: 4k, TP04P:
8ksteps X External inputs X0~X7;X10~X17 (*4) Y External outputs Y0~Y7;Y10~Y17 M0~M511, 512 points max, (*1) M768~M999, 232 points max, (*1) M2000~M2047, 48 points max, (*1) Total 4096 points General Auxiliar M M512~M767, 256 points max, (*2) M2048~M4095, 2048 points max, (*2) y relay Latched M1000~M1999, 1000 points, some are latched Special T0~T126, 127 points, (*1) T128~T183, 56 points, (*1) Total 256 points Bit 100ms Contacts (M1028=ON, T184~T199 for Subroutines, 16 points, (*1) T64~T126: 10ms) T250~T255 (accumulative), 6 points, (*1) T Timer 10ms T200~T239, 40 points, (*1) (M1038=ON, T240~T245 (accumulative), 6 points, (*1) T200~T245:
1ms) T127, 1 point, (*1) T246~T249 (accumulative), 4 points, (*1) 1ms C0~C111, 112 points, (*1) C128~C199, 72 points, (*1) Total 140 points 16-bit count up C112~C127, 16 points, (*2) C200~C223, 24 points, (*1) C224~C232, 9 points, (*2) C233~C234, 2 points, (*2) C237~C250, 14 points, (*2) C252~C255, 3 points, (*2) 32-bit count C Counter up/down Bit C235, C236 , 1 phase 1 input, 2 points (*2) Total 3 points 32bit high-speed Contacts count up/down C251, 2 phase 2 input, 1 point (*2) S0~S9, 10 points, (*2) Total 1024 points Initial step point S10~S19, 10 points (use with IST instruction), (*2) Step Zero point return S point Latched S20~S127, 108 points, (*2) General S128~S911, 784 points, (*1) Alarm S912~S1023, 112 points, (*2)