2. Programming Concepts *Note:  Default setting for starting reference of the Slave (DVP-PLC) to be read: H1064 (D100)  Default setting for starting reference of the Slave (DVP-PLC) to be written: H10C8 (D200) 6. Special D and special M corresponding to Slave ID17~ID24: (M1353 = ON, access available for up to 100 words) (Model supported: DVP-12SE V1.6 and DVP-26SE V2.0)  Default start communication address D1512 ~ D1519 to be read = H1064 (D100)  Default start communication address D1528 ~ D1535 to be written = H10C8 (D200) 7. Special D and special M corresponding to Slave ID25~ID32: (M1353 = ON, access available for up to 100 words) (Mode supported:

DVP-12SE V1.6 and DVP-26SE V2.0) 2-63 │ D115 │ D215 │ D115 │ D215 │ D115 │ D215 │ D115 │ D215 │ D115 │ D215 │ D115 │ D215 │ D115 │ D215 │ D115 │ D215 MASTER PLC SLAVE ID 17 SLAVE ID 18 SLAVE ID 19 SLAVE ID 20 SLAVE ID 21 SLAVE ID 22 SLAVE ID 23 SLAVE ID 24 Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in DVP-SE supports M1353. When M1353 is On, 32 stations in the Link and the function of reading/writing more than 16 data (SET M1353) are enabled. The user can specify the starting register for storing the read/written data in registers below.

D1576 D1592 D1577 D1593 D1578 D1594 D1579 D1595 D1580 D1596 D1581 D1597 D1582 D1598 D1583 D1599 If M1356 is ON, users can set the station numbers of slave ID17~ID24 in D1916~D1923. The master station sends commands according to the station numbers set.

D1916 D1917 D1918 D1919 D1920 D1921 D1922 D1923 Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data D1544 D1560 D1545 D1561 D1546 D1562 D1547 D1563 D1548 D1564 D1549 D1565 D1550 D1566 D1551 D1567 Start Communication Address D1512 D1528 D1513 D1529 D1514 D1530 D1515 D1531 D1516 D1532 D1517 D1533 D1518 D1534 D1519 D1535 LINK in SLAVE PLC?

M1440 M1441 M1442 M1443 M1444 M1445 M1446 M1447 Action flag for SLAVE PLC from MASTER PLC M1456 M1457 M1458 M1459 M1460 M1461 M1462 M1463 “Read/write error” flag M1472 M1473 M1474 M1475 M1476 M1477 M1478 M1479 “Reading completed” flag (turns “Off” whenever read/write a station is completed) M1488 M1489 M1490 M1491 M1492 M1493 M1494 M1495 “Writing completed” flag (turns “Off” whenever read/write a station is completed) M1504 M1505 M1506 M1507 M1508 M1509 M1510 M1511 SLAVE ID 17 SLAVE ID 18 SLAVE ID 29 SLAVE ID 20 SLAVE ID 21 SLAVE ID 22 SLAVE ID 23 SLAVE ID 24 Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 MASTER PLC SLAVE ID 25 SLAVE ID 26 SLAVE ID 27 SLAVE ID 28 SLAVE ID 29 SLAVE ID 30 SLAVE ID 31 SLAVE ID 32 Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in DVP-SE supports M1353.

When M1353 is On, 32 stations in the Link and the function of reading/writing more than 16 data (SET M1353) are enabled. The user can specify the starting register for storing the read/written data in registers below. D1584 D1600 D1585 D1601 D1586 D1602 D1587 D1603 D1588 D1604 D1589 D1605 D1590 D1606 D1591 D160 7 If M1356 is ON, users can set the station numbers of slave ID25~ID32 in D1924~D1931. The master station sends commands according to the station numbers set.

D1924 D1925 D1926 D1927 D1928 D1929 D1930 D1931 Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data Number of data D1552 D1568 D1553 D1569 D1554 D1570 D1555 D1571 D1556 D1572 D1557 D1573 D1558 D1574 D1559 D157 5 Start Communication Address D1520 D1536 D1521 D1537 D1522 D1538 D1523 D1539 D1524 D1540 D1525 D1541 D1526 D1542 D1527 D154 3 LINK in SLAVE PLC? M1448 M1449 M1450 M1451 M1452 M1453 M1454 M1455