DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Default start communication address D1520 ~ D1527 to be read = H1064 (D100) Default start communication address D1536 ~ D1543 to be written = H10C8 (D200) 8. Explanation: (16 slave stations at most can be supported.) a) PLC LINK is based on MODBUS communication protocol. b) Baud rate and communication format of all phariferal devices connected to the Slave PLC should be the same as the communication format of Master PLC, no matter which COM port of Slave PLC is used.
c) When M1356 = OFF(Default), the station number of the starting Slave (ID1) can be designated by D1399 of Master PLC through PLC LINK, and PLC will automatically assign ID2~ID16 with consecutive station numbers according to the station number of ID1. For example, if D1399 = K3, Master PLC will send out communication commands to ID1~ID16 which carry station number K3~K18. In addition, care should be taken when setting the station number of Slaves. All station numbers of slaves should not be the same as the station number of the Master PLC, which is set up in D1121/D1255.
d) When both M1353 and M1356 are ON, the station number of ID1~ID16 can be specified by the user in D1900~D1915 of Master PLC. For example, when D1900~D1903 = K3, K3, K5, K5, Master PLC will access the Slave with station number K3 for 2 times, then the slave with station number K5 for 2 times as well. Note that all station numbers of slaves should not be the same as the station number of the Master PLC, and M1353 must be set ON for this function. e) Station number selection function (M1356 = ON) is supported by versions of ES2/EX2 v1.4.2 or later, SS2/SX2 v1.2 or later, and SA2 v1.0 or later. 9. Explanation: (32 slave stations at most can be supported.
The models which are supported now are DVP-12SE V1.6 and DVP-26SE V2.0) a) PLC LINK is based on MODBUS communication protocol. b) Baud rate and communication format of all phariferal devices connected to the Slave PLC should be the same as the communication format of Master PLC, no matter which COM port of Slave PLC is used. c) When M1356 = OFF (Default), the station number of the starting Slave (ID1) can be designated by D1399 of Master PLC through PLC LINK, and PLC will automatically assign ID2~ID16 with consecutive station numbers according to the station number of ID1.
(When M1356 = ON, the station number of the starting Slave (ID1) can be designated by D1399 of Master PLC through PLC LINK, and PLC will automatically assign ID2~ID32 with consecutive station numbers according to the station number of ID1). For example, if D1399 = K3, and M1353 = Off, Master PLC will send out communication commands to ID1~ID16 which carry station number K3~K18. If D1399 = K3, and M1353 = On, In addition, Master PLC will send out communication commands to ID1~ID32 which carry station number K3~K34. In addition, care should be taken when setting the station number of Slaves.
All station numbers of slaves should not be the same as the station number of the Master PLC, which is set up in D1121/D1255. d) When both M1353 and M1356 are ON, the station number of ID1~ID32 can be specified by the user in D1900~D1931 of Master PLC.
For example, when D1900~D1903 = K3, K3, K5, K5, Master PLC will access the Slave with station number K3 for 2 times, then the slave 2-64 Action flag for SLAVE PLC from MASTER PLC M1464 M1465 M1466 M1467 M1468 M1469 M1470 M1471 “Read/write” error flag M1480 M1481 M1482 M1483 M1484 M1485 M1486 M1487 “Reading completed” flag (turns “Off” whenever read/write a station is completed) M1496 M1497 M1498 M1499 M1500 M1501 M1502 M1503 “Writing completed” flag (turns “Off” whenever read/write a station is completed) M1512 M1513 M1514 M1515 M1516 M1517 M1518 M1519 SLAVE ID 25 SLAVE ID 26 SLAVE ID 27 SLAVE ID 28 SLAVE ID 29 SLAVE ID 30 SLAVE ID 31 SLAVE ID 32 Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215