2. Programming Concepts 13. Operation flow chart: In the flow chart below, there are 16 slaves, and 50 words are accessed. Set starting reference of the S read: D1355~D1370 Set data length for reading from Slave PLC: D1434~D1449 lave PLC to be Set starting reference of the Slave PLC to be written: D1414~D1430 Set data length for writing in Slave PLC: D1450~D1465 (PLC will take default or previous setting as the set value if these registers are not specified) Disable Enable M1355 M1355 = ON, auto-detection disabled.
Set the Slave to be linked by M1360~ M1375 manually M1350=OFF, Slave ID auto-detection enabled Communication by Modbus 0X17 function Enable Disable SET M1354 RST M1354 SET M1354 Enable access up to 50 words through PLC LINK Enable access up to 16 words through PLC LINK Length of the data read/written SET M1353 RST M1353 Manual / Auto mode Enable auto mode Enable manual mode EASY PLC LINK SET M1351 SET M1352 Set times of polling cycle (D1431) SET M1350 Start to execute EASY PLC LINK 2-67