DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 14. Example 1: Connect 1 Master and 2 Slaves by RS-485 and exchange 16 data between Master and Slaves through PLC LINK a) Write the ladder diagram program into Master PLC (ID#17) Master ID# COM2 communication protocol Retain communication protocol Data length to be read from Slave ID#1 Data length to be written into Slave ID#1 Data length to be read from Slave ID#2 Data length to be written into Slave ID#2 b) When X1 = On, the data exchange between Master and the two Slaves will be automatically executed by PLC LINK.
The data in D100 ~ D115 in the two Slaves will be read into D1480 ~ D1495 and D1512 ~ D1527 of the Master, and the data in D1496 ~ D1511 and D1528 ~ D1543 will be written into D200 ~ D215 of the two Slaves. Master PLC *1 Slave PLC*2 D1480 ~ D1495 D100 ~ D115 of Slave ID#1 Read Write D1496 ~ D1511 D200 ~ D215 of Slave ID#1 D1512 ~ D1527 D100 ~ D115 of Slave ID#2 Read D1528 ~ D1543 D200 ~ D215 of Slave ID#2 Write c) Assume the data in registers for data exchange before enabling PLC LINK (M1350 = OFF) is as below: After PLC LINK is enabled (M1350 = ON), the data in registers for data exchange becomes:
2-68 M1002 MOV K17 D1121 MOV H86 D1120 SET M1120 Retain co MOV K16 D1434 MOV K16 D1450 MOV K16 D1435 MOV K16 D1451 X1 M1351 Auto mode M1350 END END MOV K17 D1121 MOV H86 D1120 SET M1120 MOV K16 D1434 MOV K16 D1450 MOV K16 D1435 MOV K16 D1451 Master PLC Preset value Slave PLC Preset value D1480 ~ D1495 K0 D100 ~ D115 of Slave ID#1 K5,000 D1496 ~ D1511 K1,000 D200 ~ D215 of Slave ID#1 K0 D1512 ~ D1527 K0 D100 ~ D115 of Slave ID#2 K6,000 D1528 ~ D1543 K2,000 D200 ~ D215 of Slave ID#2 K0 Master PLC Preset value Slave PLC Preset value D1480 ~ D1495 K5,000 D100 ~ D115 of Slave ID#1 K5,000 D1496 ~ D1511 K1,000 D200 ~ D215 of Slave ID#1 K1,000 D1512 ~ D1527 K6,000 D100 ~ D115 of Slave ID#2 K6,000