Delta Electronics DVP-ES3 — 4.9.1 Wiring DVP04PT-E2/DVP06PT-E2

Chapter 4 Installing Hardware 4.9 Wiring Temperature Measurement Modules 4.9.1 Wiring DVP04PT-E2/DVP06PT-E2 0~300 Ni100/Ni1000/Pt100/Pt1000 Cu50/Cu100/JPt100/LG-Ni1000 Ω , 0~3000 Ω Ni100/Pt100/JPt100 Cu50/Cu100 Ni1000/Pt1000/ LG-Ni1000 *3 CHX *6 O1+ I1+ ADC Shielded cable*1 I1- FE AG INA 2 Wire - Ω, 0~3000 Ω 0~300 Ni100/Ni1000/Pt100/Pt1000 Cu50/Cu100/JPt100/LG-Ni1000 CHX *6 O4+ I4+ Shielded cable*1 3 Wire - I4- FE AG 4_ *5 24V -15V AG 0V DC/DC converter +15V 24VDC *1.

Use shielded twisted pair cables for temperature sensors, including Ni100/Ni1000, Pt100/Pt1000, Cu50/Cu100, JPt100, LG-Ni1000 for analog input module wiring and keep them away from power cables and other cables that generate noise. Use 3-wire temperature sensors. But if you use two-wire temperature sensors, In-+and In- must be short-circuited (where n is between 1–6). *2. When the impedance to be measured is 0~300Ω or 0~3000Ω, it is recommended to use a 2-wire or 3-wire temperature sensor instead of a 4-wire one. *3. Choose a suitable temperature sensor.  DVP06PT-E2:

When using temperature sensors such as Ni100, Pt100, JPt100, Cu50, Cu100 and 0~300 Ω impedance sensor, the internal excitation current is 1.0389 mA. When using temperature sensors such as Ni1000, Pt1000, LG-Ni1000 and 0~3000 Ω impedance sensor, the internal excitation current is 208.3μA 。  DVP04PT-E2 : When using temperature sensors such as Ni100, Pt100 and 0~300 Ω impedance sensor, the internal excitation current is 1.53mA. When using temperature sensors such as Ni1000, Pt1000 and 0~3000 Ω impedance sensor, the internal excitation current is 200μA. 4-39