Delta Electronics DVP-ES3 — 4.9.2 Wiring DVP04TC-E2

DVP-ES3 Series Operation Manual *4. Connect FE of the shielded cable to ground when the noise it too loud. *5. Connect the terminal to ground. *6. CHX: Every channel can work with the input wiring shown above. Note 1: use cables with the same length (less than 200 m) and use terminal resistors of less than 200 ohm. 4.9.2 Wiring DVP04TC-E2 J,K,R,S,T,E,N CHX *3 + - I1+ MUX _4 S hielded cable*1 -80mV~80mV + CHX *3 - Shielded cable*1 Cold conjunction compensation *2 AG 0V 5V 24V DC/DC Converter 24VDC *1. The cable connected to the input terminal should be the cable or the shielded twisted pair cable connected to a type J, K, R, S, T, E, N thermocouple.

It should be kept separate from other power cables and cables that generate noise. *2. Connect the terminal to ground. *3. CHX: Every channel can work with the input wiring shown above. Note 1: only use copper conducting wires with a temperature rating of 60/75°C and the length must be less than 50 m. Note2: TC modules must run for 30 minutes before they start to take any temperature measurement. 4-40 I 1- F E I4 + I 4- F E