Delta Electronics DVP-ES3 — 5.3.1 DVP04AD-E2 Control Registers

Chapter 5 CPU and Module Devices 5.3. Module Device Functions 5.3.1 DVP04AD-E2 Control Registers 5_ 5-19 CR# Attrib. Register name Explanation 0 O R Model name Set up by the system: DVP04AD-E2 model code = H’0080 1 O R Firmware version Display the current firmware version in hex. format 2 O R/W CH1 input mode setting Input mode: Default = H’0000. Mode 0 (H’0000): Voltage input (±10V) Mode 1 (H’0001): Voltage input (±5V) Mode 2 (H’0002): Voltage input (0 ~ +10V) Mode 3 (H’0003): Voltage input (0 ~ +5V) Mode 4 (H’0004): Current input (±20mA) Mode 5 (H’0005): Current input (0 ~ +20mA) Mode 6 (H’0006): Current input (+4~ +20mA) Mode -1 (H’FFFF):

Channel 1 unavailable 3 O R/W CH2 input mode setting 4 O R/W CH3 input mode setting 5 O R/W CH4 input mode setting 8 O R/W CH1 sampling range Set sampling range in CH1 ~ CH4:

Range = K1 ~ K100 Default = K10 9 O R/W CH2 sampling range 10 O R/W CH3 sampling range 11 O R/W CH4 sampling range 12 X R CH1 average input value Average value of input signals at CH1 ~ CH4 13 X R CH2 average input value 14 X R CH3 average input value 15 X R CH4 average input value 20 X R CH1 present input value Present value of input signals at CH1 ~ CH4 21 X R CH2 present input value 22 X R CH3 present input value 23 X R CH4 present input value 28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of CH1 ~ CH4.

Default = K0 29 O R/W Adjusted Offset value of CH2 30 O R/W Adjusted Offset value of CH3 #31 O R/W Adjusted Offset value of CH4 34 O R/W Adjusted Gain value of CH1 Set the adjusted Gain value in CH1 ~ CH4. Default = K16,000 35 O R/W Adjusted Gain value of CH2 36 O R/W Adjusted Gain value of CH3 37 O R/W Adjusted Gain value of CH4 Adjusted Offset Value, Adjusted Gain Value: Note1: When using Mode 6 for input, the channel do NOT provide setups for adjusted Offset or Gain value. Note2: When input mode changes, the adjusted Offset or Gain value automatically returns to defaults. 40 O R/W Function: Set value changing prohibited Prohibit set value changing in CH1 ~ CH4. Default= H’0000.

41 X R/W Function: Save all the set values Save all the set values, Default =H’0000 43 X R Error status Register for storing all error status. Refer to table of error status for more information. 100 O R/W Function: Enable/Disable limit detection Upper and lower bound detection, b0~b3 corresponds to Ch1~Ch4 (0: Enable/1: Disable). Default= H’0000. 101 X R/W Upper and lower bound status Display the upper and lower bound status (0: Not exceed /1: Exceeds upper or lower bound value), b0~b3 corresponds to Ch1~Ch4 for lower bound detection result; b8~b11 corresponds