Delta Electronics DVP-ES3 — 5.3.1 DVP04AD-E2 Control Registers

DVP-ES3 Series Operation Manual ※ CR#0 for module reset You can use CR#0 to reset all the settings by simply writing H’4352 in CR#0 and wait for one second before turning the power OFF and then ON again, all the modules connected will be initialized. It is suggested to connect to only one module for module reset. And this is only available for firmware V1.10 or later. ※ CR#43: Error status value. See the table below: _5 Adjust A/D Conversion Curve You can adjust the conversion curves according to the actual needs by changing the Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37). Offset: The corresponding voltage/current input value when the digital output value = 0. Gain:

The corresponding voltage/current input value when the digital output value = 16,000.  Equation for voltage input Mode0 / Mode2: ( ) Offset Gain Offset V V X Y −     − Ч Ч = 32000 10 16000 ) ( ) (     Y=Digital output, X=Voltage input Resolution: 0.3125mV = 20V/64,000 = 10V/32,000 5-20 CR# Attrib. Register name Explanation to CH1~CH4 for upper bound detection result. 102 O R/W Set value of CH1 upper bound Set value of CH1~CH4 upper bound. Default = K32000. 103 O R/W Set value of CH2 upper bound 104 O R/W Set value of CH3 upper bound 105 O R/W Set value of CH4 upper bound 108 O R/W Set value of CH1 lower bound Set value of CH1~CH4 lower bound. Default = K-32000.

109 O R/W Set value of CH2 lower bound 110 O R/W Set value of CH3 lower bound 111 O R/W Set value of CH4 lower bound Symbols: O: When CR#41 is set to H’5678, the set value of CR will be saved. X: Set value will not be saved. R: You can use FROM instruction to read data. W: You can use TO instruction to write data.

Description bit0 K1 (H’1) Power supply error bit6 K64 (H’40) CH4 Conversion error bit1 K2 (H’2) Hardware error bit9 K512 (H’0200) Mode setting error bit2 K4 (H’4) Upper/lower bound error bit10 K1024 (H’0400) Sampling range error bit3 K8 (H’8) CH1 Conversion error bit11 K2048 (H’0800) Upper / lower bound setting error bit4 K16 (H’10) CH2 Conversion error bit12 K4096 (H’1000) Set value changing prohibited bit5 K32 (H’20) CH3 Conversion error bit13 K8192 (H’2000) Communication breakdown on next module Note: Each error status is determined by the corresponding bit (b0 ~ b13) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error