Delta DVP-ES3 — 5.3.3 DVP06XA-E2 Control Registers

DVP-ES3 Series Operation Manual Adjust A/D Conversion Curve You can adjust the conversion curves according to the actual needs by changing the Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37). Offset: The corresponding voltage/current input value when the digital output value = 0. Gain: The corresponding voltage/current input value when the digital output value = 16,000.  Equation for voltage input Mode0 / Mode2: ( ) Offset Gain Offset V V X Y −     − Ч Ч = 32000 10 16000 ) ( ) (     Y=Digital output, X=Voltage input Resolution: 0.3125mV = 20V/64,000 = 10V/32,000 _5  Equation for voltage input Mode1 / Mode3:

( ) Offset Gain Offset V V X Y −     − Ч Ч = 32000 5 16000 ) ( ) (     Y=Digital output, X=Voltage input Resolution: 0.15625mV = 10V/64,000 = 5V/32,000  Equation for current input Mode4 / Mode5: ( ) Offset Gain Offset mA mA X Y −     − Ч Ч = 32000 20 16000 ) ( ) (     Y=Digital output, X=Current input Resolution: 0.625μA = 40mA/64,000 = 20mA/32,000  Equation for current input Mode6:  − Ч Ч = ) ( ) ( mA mA X Y     ( ) 6400 19200 6400 32000 20 16000 −    Y=Digital output, X=Current input Resolution: 0.5μA = 16mA/32,000 5-30 Description bit5 K32 (H’20) CH3 Conversion error bit13 K8192 (H’2000) Communication breakdown on next module Note:

Each error status is determined by the corresponding bit (b0 ~ b13) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error