Delta Electronics DVP-ES3 — 8.2.2.1 Options - System Information Page

Chapter 8 Hardware Configuration System Parameter On the System Parameter page, you can set parameters by entering appropriate values or by selecting from a list.  Clear Non-latched area when Run  Stop This determines whether the states and values of the non-latched devices are cleared when the PLC changes from Run to Stop.  Disable: all the states and values in the non-latched devices stay the same.  Enable: all the states and values in the non-latched devices are cleared and restored to defaults.  Y keeps outputting when RUN  Stop This determines the states of the Y devices when the CPU module begins to run or stop.  Retain: the states of the Y devices stay the same.  Off:

all Y devices are set to OFF.  Setting delay time to detect I/O Module This sets the time to detect an I/O module after powering on the CPU module. 8_  Assign X Input Point Control Run/Stop This assigns an input point to have the CPU module run or stop.  Disable : run or stop the CPU module with the dip switch of the CPU module.  Enable : run or stop the CPU module with the assigned input point, and the dip switch of the CPU module still controls the run stop state of the CPU module. 8-7