Delta Electronics DVP-ES3 — 8.2.2.1 Options - System Information Page

DVP-ES3 Series Operation Manual  Select X Input Point If you select Enable in the previous option, you can select one input point to control the Run or Stop state of the CPU module from the dropdown list.  Constant Scan Cycle Time This sets the minimum scan cycle time.  Disable : disables this function.  Enable : when the actual scan cycle time is less than the setting time, the CPU module waits until the setting time is met, and then starts the next scan. When the actual scan time is longer than the setting time, the CPU module starts the next scan after the actual scan time completes.  Input Constant Time If you selected Enable in the previous option, you set the scan cycle time here.

If the actual scan time is larger than the setting time, a watchdog timeout occurs when the CPU module operates.  Setting Watchdog Time This parameter sets a timeout during which the program is scanned. The CPU module sends an error if the program execution exceeds the watchdog time.  Save Error History Info This specifies where to store the error log.  PLC : store error logs in the PLC. The PLC can store up to twenty error logs. If there are more than twenty error logs, the oldest error log is overwritten by the latest error log.  PLC & SD Card :

when there are more than twenty error logs, the oldest error log is backed up to the memory card before the oldest error log is overwritten in the PLC.  COM Communication Error Record _8 This parameter sets whether to enable the error record when there is an error at the COM port.  Disable : disables this function.  Enable : enables this function and starts recording COM errors in the error log.  Select Action When 24 Vdc Input Unstable What to do when the 24 Vdc power is unstable  Continue Running when power stable: waits till the power is stable and then PLC begins to run.  Into Error Status: Stops and go to the error mode 8-8