Delta DVP-ES3 — 8.2.2.2 Options - COM1 & COM2 Port Setting

Chapter 8 Hardware Configuration 8.2.2.2 Options - COM1 & COM2 Port Setting The DVP-ES3 Series CPU module has two communication ports. There are two areas to set the parameters, one for each communication port.  Set a station address. You can identify a device on a network by the station address. The station address cannot be the same as the station address for another device on the same network. If the communication port functions as a slave, and there are other slaves, the station address of the communication port cannot be 0. Station address 0 broadcasts to all slaves in a communication protocol.

If a master specifies in a data packet that data must be sent to station address 0, the data is sent to all slaves. No matter what the station address of these slaves are, these slaves receive the data packet addressed to station address 0. 8_  Set when the communication port runs. Select Stop --> Run , and communication works when the CPU module switches from Stop to Run. If you instead select Power-on , the communication starts working when you Power-on the module.  Select a communication speed in the Baud Rate list, or select Custom and enter a new rate.  Set the communication parameters for the port.

 Set the Delay Time to Reply when the DVP-ES3 CPU module receives communication and how long it waits before responding to the remote modules. 8-13 9/30 23:59:59 22:59:59 10/01 00:00:00 (9/30) 23:00:00 : (to) : (to) : (to) 10/01 00:59:59 (9/30) 23:59:59 10/01 00:00:00 00:00:00 Normal 10/01 00:00:01 00:00:01