Delta DVP-ES3 — 8.2.2.4 Options - Ethernet Port Advanced Setting

DVP-ES3 Series Operation Manual  Received Data Timeout applies when the DVP-ES3 Series CPU module acts as a server to send out communications. The timeout is how long the module waits before the received data times out. 8.2.2.3 Options - Ethernet Port Basic Setting Click Ethernet Port Basic Setting to see the setup page. Set the communication parameters for the Ethernet port in the CPU module on this page. Select Static in the Mode list to specify an IP address. Select Dynamic or BOOTP in the Mode list to assign an IP address from a DHCP/BOOTP server. 8.2.2.4 Options - Ethernet Port Advanced Setting Click Ethernet Port Basic Setting to see the setup page.

There are setups for IP Filter, NTP, Email, Socket, and RTU mapping . IP Filter _8 Devices whose IP addresses are listed in the table are allowed to communicate with the CPU module; the CPU module discards data packets sent from devices whose IP addresses are not in the table. Devices on a network are filtered. This setting ensures that objects communicating with the CPU module are known devices. You can set up to 8 address ranges for allowed devices. 8-14