DVP-ES3 Series Operation Manual 8.3 Data Exchange 8.3.1 Device Settings Dialog Box Descriptions In the Device Settings dialog box, after you click the Data Exchange-COM1, Data Exchange-COM2 or Data Exchange-Ethernet tab, you can set the parameters for the data exchange table for the communication port built into the DVP-ES3 Series module. COM2 using the Modbus protocol, or through an Ethernet port using the Modbus TCP protocol. The DVP-ES3 Series module can be a master and exchange data with remote slave devices through COM1 and When you set the start Mode to Program Control, the program in the PLC determines whether to perform the set data exchange.
PLC Run means that the set data exchange is performed automatically when PLC is in the RUN state. Always Enable means that the data exchange is performed constantly when the PLC is powered on. Add a new row in the data exchange table in area by clicking Add . Move the selected data exchange row up or down by clicking Move Up and Move Down . Delete the selected data exchange row by clicking Delete . Copy the selected data exchange row by clicking Copy. You can then paste it back into the table as the last row. _8 The following table explains the columns in the data exchange table.
8-24 Name Description Item The number of the block for data exchange Enable Selects whether to enable the data exchange table when the data exchange is performed. Station Address/ IP Address The slave station address for the data exchange table. You can set one address for multiple data exchange tables. It is a station address under the COM1 and COM2 tabs,