DVP-ES3 Series Operation Manual 3) Note the limitation on the length of the CANopen network. The transmission distance of the CANopen network depends on the transmission rate of the CANopen network. The following table shows the relation between the transmission rate and the maximum communication distance. 4) The list below shows the Delta network products for the CANopen network.
_10 10-8 Transmission rate 20K 50K 125K 250K 500K 1M (bit/seconds) Maximum 2500 1000 500 250 100 25 communication distance (meters) Product Model Function AS332T-A AS332P-A AS324MT-A AS320T-B AS320P-B AS300N-A The AS300 series PLC can function as the CANopen master or slave when you install an AS-FCOPM function card. The AS-FCOPM is equipped with a 120 ohm resistor controlled by a switch. AS228T-A AS228P-A AS228R-A AS218TX-A AS218PX-A AS218RX-A AS200 Series PLC is built with CAN communication port. The CAN port conforms to the basic communication protocol CANopen DS301. It supports master and slave modes. The CAN communication terminal is equipped with a 120 Ω resistor.
You can use a short circuit to use this resistor. DVP32ES300R DVP32ES300T DVP32ES311T DVP48ES300R DVP48ES300T DVP64ES300R DVP64ES300T DVP80ES300R DVP80ES300T The DVP-ES3 Series PLC has a built-in CAN interface. It can function as the CANopen master or slave. DVP32ES200RC DVP32ES200TC The DVP-ES2-C series PLC has a built-in CAN interface. It can function as the CANopen master or slave. DVPCOPM-SL DVPCOPM-SL is a module connected to the left side of an S series PLC. It can function as the CANopen master or slave. The PLCs that you can connect to the DVPCOPM-SL are the DVP-28SV, DVP-28SV2, DVP-SX2, DVP-SA2, and DVP-EH2-L.