Delta DVP-ES3 — 10.5.1 CANopen Network Node State Display

Chapter 10 CANopen Function and Operation 10.5 Troubleshooting 10.5.1 CANopen Network Node State Display 1. In the DVP-ES3 Series PLC, while you enable the CANopen function, it uses SR825–893 as the special registers as shown in the following table. 2. As a master, the DVP-ES3 Series PLC supports a maximum of 64 slaves ranging from node 1 to node 64. You can use SR826–829 to monitor the state of the nodes in the network. The 16 bits in SR826 correspond to 16 slaves and their corresponding relations are shown in the following table.

When the node in the master node list is normal, the corresponding bit is OFF; when the node in the master node list is abnormal (for example, initializing fails or the slave is offline for some reason), the corresponding bit is ON. 3. The error code of every node is displayed through the corresponding special register (SR830–893) and the relations between special register and corresponding node (1–16) is shown in the following table. (You can also judge for other correspondings that are not listed here.) 4. Node codes displayed in SR830–893 when the ASSeries PLC is the master:

10 10-27 Special register Function SR825 Displays the state of CANopen DS301 Master SR830–SR893 Displays the state of 64 nodes in the network SR826 Flag for the state of the slave 1–16 SR827 Flag for the state of the slave 17–32 SR828 Flag for the state of the slave 33–48 SR289 Flag for the state of the slave 49–64 SR821 Version of CANopen DS301 SR822 Displays the CANopen baud rate (unit:

1kpps) Bit b7 b6 b5 b4 b3 b2 b1 b0 Node Node 8 Node 7 Node 6 Node 5 Node 4 Node 3 Node 2 Node 1 Bit b15 b14 b13 b12 b11 b10 b9 b8 Node Node16 Node15 Node14 Node13 Node12 Node11 Node10 Node 9 Special register SR830 SR831 SR832 SR833 SR834 SR835 SR836 SR837 Node Node 1 Node 2 Node 3 Node 4 Node 5 Node 6 Node 7 Node 8 Special register SR838 SR839 SR840 SR841 SR842 SR843 SR844 SR845 Node Node 9 Node10 Node11 Node12 Node13 Node14 Node15 Node16 Code Indication How to correct 0 The node is error free or the node is not configured. N/A