Delta DVP-ES3 — 10.5.1 CANopen Network Node State Display

DVP-ES3 Series Operation Manual 5. Codes displayed in SR825 when the DVP-ES3 Series PLC is the master: _10 10-28 Code Indication How to correct E0 ASSeries PLC master module receives the emergency message sent from slave. Read the relevant message with the PLC program E1 PDO data length returned from the slave is not consistent with the length set in the node list. Set the PDO data length of the slave and re-download. E2 PDO of slave is not received. Check and ensure the setting is correct. E3 Downloading auto SDO fails. Check and ensure auto SDO is correct. E4 Configuration of PDO parameter fails. Ensure that the PDO parameter setting is legal. E5 Error in key parameter setting.

Ensure that the connected slave device is consistent with the configured slave in the software. E6 The slave does not exist in the network Ensure that the power supply of slave is normal and slave is correctly connected to the network. E7 Slave error control is timed-out. E8 The node IDs of master and slave repeat. Set the node ID of the master and slave again and ensure their node IDs are unique. Code Indication How to correct 0 In CANopen DS301 mode: the PLC works as master and is working normally. Not in CANopen DS301 mode: the master mode function is not activated. N/A F1 No slave in the list Add slave into the node list and then re-download the configuration data.

F2 The data are being downloaded to the PLC Wait to finish downloading the configuration data. F3 The configuration receiving error in the PLC Download parameter configuration again. F4 Bus-OFF is detected. Check that the CANopen bus cables are properly connected and ensure that all the node devices run at the same baud rate before you reboot. F5 The PLC setting error such as incorrect node address The node address in the DVP-ES3 Series PLC should be between: 1–127. F8 Internal error; the error is detected in the internal memory If the same error occurs after cycling the power, replace it with a new DVP-ES3 Series PLC. FB The sending buffer in the PLC is full.

Check that the CANopen bus cable is properly connected and then reboot. FC The receiving buffer in the PLC is full. Check that the CANopen bus cable is properly connected and then reboot.