Delta Electronics DVP-ES3 — 10.6 Application Example

Chapter 10 CANopen Function and Operation 3. Setting the CANopen Baud Rate and Node ID of DVP-ES3 Series PLC The DVP-ES3 Series PLC uses the default setting values: Node ID: 1 and baud rate: 1Mbps. You set the CANopen Node ID and baud rate for the DVP-ES3 Series PLC in the CANopen Builder software, as shown in the following steps. A. In ISPSoft, double-click HWCONFIG in the project management area to start HWCONFIG . B. Click CANopen Builder . C. IF DVP-ES3 is in master mode, you can skip this step. If not, you can go to Properites and set it in seconds and supply power again and then proceed to the next step. Master mode. After that download the parameter to DVP-ES3.

Set DVP-ES3 Power off for 2 10 10-31