DVP-ES3 Series Operation Manual 4.4 Wiring Warnings _4 Things to note while wiring an I/O module (1) Terminal definitions ◆ Two-/three-wire (passive sensor): the sensor and the system share the same power circuit. ◆ Four-wire (active sensor): the sensor uses an independent power supply and should not share the same power circuit with the system. (2) Terminals with insulation sleeves cannot be used as a terminal block. It is recommended that the terminals be covered with insulation tubes. (3) Use single-wire cables or two-wire cables with a diameter of 24 AWG to 22 AWG (2mm) and with less than 1mm pin-type terminals. Only use copper conducting wires with a temperature rating of 60/75 ° C.
24-22AWG 8-10mm 4-8 Before installing or wiring a module, you must verify that the external power supply is turned off. If the power supply is not turned off, you may get an electric shock, or the product may be damaged. After you complete installing or wiring the module, make sure that a terminal block cover is installed on the module before turning on the power supply or operating the module. If the terminal block cover is not installed properly, you may get an electric shock, or the module may not operate normally. Be sure to connect the terminals FG and LG / with protective grounding conductors. Otherwise, you may get an electric shock, or the module may not operate normally.
To ensure that a PLC is wired correctly, you must check the rated voltage of the product and the arrangement of the terminals. If the PLC is connected to a power supply that does not conform to the rated voltage, or the product is not wired correctly, a fire may occur, or the product may be damaged. The external connections should be crimped, press-welded by specific tools, or soldered correctly. Improper connections may result in a short circuit, fire, or malfunction. Tighten the terminal screws to the specified torque. If the terminal screws are loose, a short circuit, fire, or faulty operation may occur.
Tightening the terminal screws too far may cause damage to the terminal screws or the module, resulting in a short circuit or malfunction. Make sure there are no foreign substances such as iron filings or wiring debris inside the module. Foreign substances may result in a fire, damage, or malfunction.