Chapter 4 Installing Hardware 4.6.1.3 Open-collector Input Types Sinking (NPN input type) NPN Souring (PNP input type) 4_ PNP 24VD C 4.6.1.4 Two-wire Proximity Switch Use the two-wire proximity switch whose leakage current IL is less than 1.5 mA when the switch is OFF. If the leakage current is larger than 1.5 mA, connect the divider resistance Rb using the formula below. 5.1 6 − ≤ IL Rb ( k Ω ) Sinking I/O Two-wir e Proxim ity Sw itch 4-15 +Vcc Internal circuit 0V I/O X0 Inter nal circuit S/ S + 24VDC +Vcc Internal cir cuit 0V I/O X0 Internal Circuit S/S + 0V + I L X0 Internal C ircuit S/S Rb + 24VDC S/S