Delta DVP-ES3 — 6.27.2 Explanation of CANopen Communication Instructions

Chapter 6 Applied Instructions 5. SM1681 is set to OFF when you execute this instruction on servos ( S is 1–8). SM1681 is set to ON when the initializations are complete. SM1683 is set to OFF when you execute this instruction on inverters ( S is 21–28). SM1683 is set to ON when the initializations are complete. 6. SM1682 is set to ON when an error occurs during communication. In addition, SR658 retains the number of the axis in which the error occurs and SR659 retains the error code. (The flag and code here are especially for Delta CANOpen Communication Instructions.) 7.

If a heartbeat error (SR0 = 0x1900~0x191C; last 2 codes are the slave ID) occurs after the initialization is complete and the SM1684 is OFF (default, indicating when one goes down, all the servos are OFF), the initialization complete flags SM1681 & SM1683 will be cleared to OFF and related actions on other slaves will also be paused. After all the troubles are cleared, you need to initialize every slave to restart the operation. PLC will turn the error LED off after PLC confirms the initialization is complete. This error will be recorded in the error log. 8.

If the axes are working independently and the communication is working properly, you can set the SM1684 to ON (indicating when one goes down, only the defective servo is OFF) to notify PLC to record the specific error on the error log and other slaves can keep working. 9. You need to set the communication station and speed of the servos manually and then turn the servos off and then on again to activate the new parameters. 10. This instruction should not be used in the Structured Texts programming language, or interrupt programs or FB programs that only be called once.

6_ Initialization and operation process chart 6-875 HWCONFIG CA N Port Work Mode PLCRun P LC sending initialization No Initialization Set up error record complete ex: Serv o, VF D disconnected Set up initialization complete PLCRun flags M1681 & M1683 Clear initialization complete Wait for flags M1681 & M1683 the P LC to run PLCStop Determine if the heartbeat Abnormal works normally Stop heartbeat function and stop servo & VFD Normal Still Run Execute the communication PLC Stop Clear initialization complete instructions for positioning flags M1681 & M1683 Execute the communication instructions for positioning Clear initialization complete flags M1681 & M1683