Delta DVP-ES3 — 6.27.2 Explanation of CANopen Communication Instructions

DVP-ES3 Series Programming Manual controlled by the software, and EDI10–EDI14 are controlled by the hardware. D. Reset P4-07 (SDI status controlled manually) to 0. E. Set P2-36 (EDI9) to 16#0101. This indicates that the function of EDI9 is set to Servo ON. F. Set P0-17 (CM1A) to 1. This indicates that the mapping parameter is the pulse command output register CMD_O. G. Set P0-18 (CM2A) to 64. This indicates that the mapping parameter is the pulse command register CMD_E. H. Set P5-20–P5-35 (acceleration time) to 1. This indicates that the acceleration time is 1 ms. I. Set P5-60–P5-75 (target speed) to 1. This indicates that the target speed is 0.1 rpm. J.

Set PDO1 to correspond to P5-07 (PR command), P0-01 (Fault code), P0-46 (state of DO point) and P4-07 (state of DI point) K. Set PDO2 to correspond to P0-09 (CM1 state: CMD_O) and P0-10 (CM2 state: CMD_E). L. Set PDO3 to correspond to P0-11 (CM3 state: state of current torque) M. Set time for the heartbeat and the PLC scan overtime to 200ms (default). When a communication overtime occurs, PLC will send error message (error LED flashing slowly; refer to error code for more details) and the servo turns off automatically. N. If SM1685 is ON, PDO3 reads self-defined parameters from servo drive P0-12 and stores the data in _6 SR791-SR806. You need to set up the P0-20 (CM4A) before executing.

2 SRs are reserved for every servo drive axis and you can define their data types. 5. Do not use the COPRW instruction (API 2807) to modify the servo parameters of the eight items A, B, F, G, J, K and N above after initialization. 6. When you use an absolute-type servo, use the COPRW communication instruction to write 16#0100 to P3-12, which writes the relevant absolute-type servo parameters to EEPROM at the moment the servo powers off. 7. Set the relevant DI signal configuration parameters manually or with the COPRW instruction to modify the hardware DI signal setting of ASD-A2.

Use COPRW to modify the configuration after execution of the INITC instruction is complete and before the servo is enabled. 8. When the initialization is complete, the servo is in the PR mode. Do not make any communication control on servo P5-18. 9. For more details on the servo parameters, refer to the Delta Servo Operation manual. 6-878