Delta DVP-ES3 — 6.27.2 Explanation of CANopen Communication Instructions

Chapter 6 Applied Instructions Example of Communication with Delta Inverter 1. Manually set the inverter parameter P09-36 (ranging from 21 to 28), P09-37 (communication baud rate default is 1MHz) and P09-40 to standard CANopen protocol (default). 2. Manually set the source of frequency command P00-20 to 6 and source of the operation command P00-21 to 3, and have them controlled by CANopen communication. 3. The following list shows the settings to initialize an inverter in the ES3 Series. A. Set PDO mapping area: the operation frequencies, current state, and states of torque and DI point correspond to PLC SRs. B. Set time for the heartbeat and the PLC scan overtime to 200ms (default).

When a communication overtime occurs, PLC will send error message (error LED flashing slowly; refer to error code for more details) and the servo turns off automatically. 4. For more details on the servo parameters, refer to the Delta Inverter Operation manual. Example 6_ 1. When M0 changes from OFF to ON, the INITC instruction starts to initialize the inverter at station address 21, until SM1683 is ON. When SM1683 is ON, it indicates the initialization is complete. Additional Remarks: When you use Delta Special Driver and execute INITC instruction, the baud rate and time to synchronize is shown below.

If you use Delta Special Driver & CANopen DS301 modes, you can use CANopen Builder to modify the time to synchronize, but be sure to modify the time less than it is shown below. 6-879 Baud Rate (bps) 1M 500K 250K 125K Time to Synchronize (ms) 10 15 30 60