Delta DVP-ES3 — 6.27.2 Explanation of CANopen Communication Instructions

Chapter 6 Applied Instructions Symbol 6_ S 1 : Station address of servo or slave S 2 : Request code S 3 : Index S 4 : Sub-index S 5 : Read/write device D : Communication completion flag Explanation 1. This instruction reads and writes CANopen communication data to the servo at the address specified in S 1 . The range of S 1 is 1–127. If the value is out of range ( 127), the minimum or maximum value is automatically processed by the instruction as the value of S 1 . 2. S 2 can only specify four types of request codes, as shown in the following table. If you set the request code wrong, it does NOT execute; SM1682 is ON and SR659 is 16#0005.

6-901 API Instruction Operand Description 2807 COPRW S 1, S 2, S 3, S 4, S 5, D Reading and writing CANopen communication data Device X Y M S T C HC D FR SM SR E K 16# “$” F S1    S2     S3     S4     S5  D     BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1    S2    S3    S4    S5    D  Pulse instruction 16-bit instruction 32-bit instruction - ES3 -