Chapter 6 Applied Instructions 7. The COPRW instruction supports all CAN port work modes. 8. Most of the parameters in Delta ASDA-A2 are displayed in the decimal format. You can convert the parameters into index addresses, see the example below. 0 is a fixed value for the sub index address. Example: The index address of PX-YY=0x2000 + ( X ) + YY P2-10 = 0x2000 + ( 0x0002 ) + 0x000A = 0x220A P5-04 = 0x2000 + ( 0x0005 ) + 0x0004 = 0x2504 6_ P1-44 = 0x2000 + ( 0x0001 ) + 0x002C = 0x212C 9. Most of the parameters in Delta inverter are also displayed in the decimal format. Use the following formula to convert the parameters. Example:
The index address of PXX-YY=0x2000 + XX (hexadecimal); The sub index address is YY+1 (hexadecimal) The sub index address is 0x0F+1= 0x10 The index address of P10-15 = 0x2000 + 0x000A = 0x200A 10. Since this instruction uses SDO (Service Data Objects) and the communication mode is one transmission (one sending/one receiving) at a time, it is not suggested to use 2 COPRW instructions at a time in one scan cycle. And it is not suggested to use this instruction in a function block. Because when this instruction is written in a function block, there will be 2 POU in the PLC program and when the function block is called, 2 instructions will be enabled at the same time. 6-903