DVP-ES3 Series Programming Manual The setting value of Delta servo homing mode is a hex value. The value is defined as the format of 0xWZYX. See the explanation of respective codes as below. _6 6-912 Homing Range Function and code description Remark mode code W 0 ~ 1 Select the final position where the servo stops. 0 = The servo leaves the original point, decelerates and stops and then automatically returns to the real original point. 1 = After leaving the original point, decelerating and stopping, the servo will not perform any action any more. Z 0 ~ 1 Handling mechanism when the limit is encountered. 0 = Output stops. 1 = Output is conducted in the reverse direction.
Y 0 ~ 2 Z pulse signal setting (used for X code 0~8 ) 0 =Look for Z pulse when coming back. Do not look for Z phase when going forward. 1 =Go forward to Z pulse. Do not look for Z pulse when coming back. 2 =Do not look for Z pulse. Z pulse signal handling method (applicable to X code: 9~A) 0 =Look for Z pulse when coming back. 1 =Do not look for Z pulse both when coming back and going forward. X 0 ~ A Homing method: 0~8 0 = Homing in the forward direction; PL is the original point 1 = Homing in the reverse direction; NL is the original point. 2 = Homing in the forward direction; ORGP: OFF > ON, as the original point. 3 = Homing in the reverse direction; ORGP: OFF > ON, as the original point.
4 = Homing in the forward direction; look for Z pulse and regard it as the original point. 5 = Homing in the reverse direction; look for Z pulse and regard it as the original point. 6 = Homing in the forward direction; ORGP: ON > OFF, as the