Chapter 6 Applied Instructions Symbol Node : Specified node ID Mode : Homing mode code Ok : Completion flag 6_ Err : Error flag Explanation 1. Make sure that all Delta drives have been initialized before executing the reset instruction. 2. The value of Node is in the range of 1~8 (exclusive to servo node IDs). If the setting value exceeds the range, the PLC will not perform the action of the homing mode and set the Err flag to ON. (Refer to explanation of SR659 for error codes.) 3. The ZRNM instruction can set the homing mode of only one drive every time. If multiple instructions are enabled simultaneously, the PLC will take priority to perform the instruction which is enabled earlier. 4.
The ZRNM instruction is executed to send the command when it is enabled. If the instruction is disabled before the Ok flag is on, the PLC will not set the Ok flag to ON. 5. Mode sets a homing mode. If the setting value exceeds the range, the PLC will still send the command and the server itself will decide whether to receive the command or not. The setting mode is the homing mode that ASDA servo parameter P5-04 corresponds to.
6-911 API Instruction Operand Description 2810 ZRNM Node,Mode,Ok,Err Setting the homing mode for Delta servo Device X Y M S T C HC D FR SM SR E K 16# “$” F Node Mode Ok Err BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type Node Mode Ok Err Pulse Instruction 16-bit instruction 32-bit instruction - ES3 -