DVP-ES3 Series Programming Manual 5. The setting value of Para is NOT applicable to Delta special driver mode. The settings for Para (NMT service code) are listed in the following table. If the setting value is not one of the values in the table, the Err flag turns on. 6. The RSTD instruction can implement the command action on only one drive or slave every time. If multiple RSTD instructions are enabled simultaneously, the PLC will automatically take priority to perform the instruction which is enabled earlier. 7. The RSTD instruction is executed to send the command when it is enabled. If the instruction is disabled before the Ok flag is on, the PLC will not set the Ok flag to ON. 8.
Apart from notifying the specified drive to clear the error state, the instruction would also re-check if relevant communication parameter values are correct and re-set correct communication parameter values. For example, due to the disconnection of the slave of station address 2, the entire system stops running. After the trouble is solved, the slave of station address 2 can return to the state of being controllable by using the RSTD instruction to reset the slave of station address 2 only. So the time of re-initializing all drives are saved. 9.
If the slave responds by sending back any communication command fault to the PLC during the communication, the RSTD instruction will turn the Err flag on and stop the upcoming actions. (Refer to explanation of SR659 for error _6 codes.) 6-910 NMT 16#01 16#02 16#80 16#81 16#82 service code Function description Function Start the slave Stop the slave Enter the pre-operational state Reset the application layer Reset the communication description