Delta DVP-ES3 — 6.27.2 Explanation of CANopen Communication Instructions

Chapter 6 Applied Instructions Symbol Node : Station address which is reset Para : Setting value of the parameter 6_ Ok : The reset completion flag Err : The reset error flag Explanation 1. Before the RSTD instruction is used in Delta special instruction mode, make sure that all Delta drives have been initialized via the INITC instruction and they once worked normally. 2. When used in CANopen DS301 mode, the RSTD instruction works as the NMT communication function and can switch network states via the Para parameter. 3. When CAN communication port is specified to work in Delta special driver mode, the value of Node can be 0 (for the motor drives only.

When the station address exceeds the range, the PLC will not perform the reset action and the broadcast function) and 1~8 which are for servo station addresses only and 21~28 for station addresses of AC Err flag turns on. (Refer to the explanation of SR659 for error codes) 4. When CAN communication port is specified to work in CANopen DS301 mode, the value of Node is in the range of 1~64 and 0 (for the broadcast function). When the value exceeds the range, the PLC will not perform the NMT communication and the Err flag turns on.

(Refer to the explanation of SR659 for error codes) 6-909 API Instruction Operand Description 2809 RSTD Node,Para,Ok,Err Sending Reset or NMT command Device X Y M S T C HC D FR SM SR E K 16# “$” F Node    Para    Ok    Err    BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type Node  Para  Ok  Err  Pulse Instruction 16-bit instruction 32-bit instruction - ES3 -