Delta DVP-ES3 — 7.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds

Chapter 7 Troubleshooting 7.2 Troubleshooting for CPU Modules Check the LED indicators and the error codes from the CPU module and refer to the following table for troubleshooting. V in the Log column indicates the error is recorded in the log. X in the Log column indicates the error is not recorded in the log. H in the Log column indicates whether or not you can set recording the error in the log in HWCONFIG. 7.2.1 ERROR LED Indicators Are ON 7.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds 7_ 7-5 Error Code Description Solution Flag Log (16#) 000A Scan timeout 1. Check the setting of the watchdog timer in HWCONFIG. 2.

Check whether the program causes a long scan time SM8 V Error Code Description Solution Flag Log (16#) 000C The program in the PLC is damaged. Download the program again. SM9 V 0010 CPU memory is denied. Contact the factory. SM9 V 002E CPU external memory access is denied. Contact the factory. SM9 V 002F PLC programs are not consistent with the system logs. Download the program again. SM34 V 0102 The interrupt number exceeds the range. Check the program, compile the program again, and download the program again. SM5 X 0202 The MC instruction exceeds the range. Check the program, compile the program again, and download the program again. SM5 X 0302 The MCR instruction exceeds the range.

Check the program, compile the program again, and download the program again. SM5 X 0D03 The operands used in DHSCS are not used properly. Check the program, compile the program again, and download the program again. SM5 X 0E05 The operands HCXXX used in DCNT are not used properly. Check the program, compile the program again, and download the program again. SM5 X 200A Invalid instruction Check the program, compile the program again, and download the program again. SM5 V 6010 The number of MODBUS TCP connections exceeds the range. Check the number of superior devices (maximum is 32). SM 1092 V 6011 The number of EtherNet/IP connections exceeds the range.

Check the number of connections (maximum is 16). SM 1093 V C000 - CFFF The program syntax is incorrect. Save the PLC program and hand the file to the company or the technicians.