DVP-ES3 Series Programming Manual 7.2.3 ERROR LED Indicators Blinking Rapidly Every 0.2 Seconds This happens when the power supply 24 VDC of the CPU module is disconnected, or the power supply is not sufficient, not stable or abnormal. 7.2.4 ERROR LED Indicators Slow Blinking Every 3 Seconds and Lighting up for 1 Second 7.2.5 The LED RUN and ERROR Indicators are Blinking Simultaneously Every 0.5 Seconds This happens when the firmware of the CPU module is being upgraded. If this happens once the power is supplied to the CPU module, it means errors occurred during the previous firmware upgrade. Users need to upgrade the firmware again or contact your point of purchase.
7.2.6 The RUN and LED Indicators are Blinking One After Another Every 0.5 Seconds. This happens when the CPU module memory card is backing up, restoring, or saving. _7 7.2.7 Other Errors (Without LED Indicators) 7-6 Error Code Description Solution Flag Log (16#) 002A The external voltage is abnormal. Check whether the external 24 V power supply to the module is normal. SM7 V Error Code Description Solution Flag Log (16#) 1900 - 191C Heartbeat errors occurred in the slave for the Delta ASD-A2 control. 1. Check the CANopen connection cable. 2. Check if the specific slave is working properly. Note:
The last 2 digits of the error code represent the ID number of the slave (convert hexadecimal to decimal). - V Error Code Description Solution Flag Log (16#) 0011 The PLC ID is incorrect. Check the PLC ID. SM34 V 0012 The PLC password is incorrect. Check the PLC password. SM34 V 002D The PLC maximum password attempts exceeded. Reset the CPU module or restore the CPU module to its factory settings. SM34 V 0050 The memories in the latched special auxiliary relays are abnormal. 1. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 2. If the error still occurs, contact the factory.
SM6 V 0051 The latched special data registers are abnormal. 1. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. SM6 V