Chapter 7 Troubleshooting 7_ 7-7 2. If the error still occurs, contact the factory. 0052 The memories in the latched auxiliary relays are abnormal. 1. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 2. If the error still occurs, contact the factory. SM6 V 0054 The latched counters are abnormal. 1. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 2. If the error still occurs, please contact the factory. SM6 V 0055 The latched 32-bit counters are abnormal. 1.
Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 2. If the error still occurs, contact the factory. SM6 V 0056 The latched special auxiliary relay is abnormal. 1. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 2. If the error still occurs, contact the factory. SM6 V 0059 The latched data registers are abnormal. 1. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 2. If the error still occurs, contact the factory.
SM6 V 005D The CPU module does not detect a memory card. Check that the memory card is inserted correctly into the CPU module. SM453 V 005E The memory card is initialized incorrectly. Check whether the memory card is broken. SM453 V 0063 An error occurs when data is written to the memory card. Check whether the file path is correct or whether the memory card is malfunctioning. SM453 V 0064 A file in the memory card cannot be read. Check whether the file path is correct, or whether the file is damaged. SM453 V 1950 The initialization of the Delta ASD-A2 control has not yet been completed, the CANopen instructions cannot be executed. 1. Check the CANopen connection cable. 2.
Check if the specific slave is working properly. 3. If nothing is wrong, initialize the Delta ASD-A2 again. - V 2001 Not in the right mode for the ASDA-A2 while using the CANopen communication instruction. Check if the CANopen operation mode is correct. SM0 V 2003 The device used in the program exceeds the device range. Check the program, compile the program again, and download the program again. SM0 V 200B The operand n or the other constant operands K/H exceed the range. Check the program, compile the program again, and download the program again. SM0 V 200C The operands overlap. Check the program, compile the program again, and download the program again.
SM0 V 200D The binary to binary-coded decimal conversion is incorrect. Check the program, compile the program again, and download the program again. SM0 V 200E The string does not end with 00. Check the program, compile the program again, and download the program again. SM0 V 2012 Incorrect division operation Check the program, compile the program again, and download the program again. SM0 V 2013 The value exceeds the range of values that can be represented by the Check the program, compile the program again, and download the program again. SM0 V