Delta DVP-ES3 — 7.2.7 Other Errors (Without LED Indicators)

DVP-ES3 Series Programming Manual _7 7-8 floating-point numbers. 2014 The task designated by the TKON or YKOFF instruction is incorrect or exceeds the range. Check the program, compile the program again, and download the program again. SM0 V 2017 The instruction BREAK is written outside of the FOR-NEXT loop. Check the program, compile the program again, and download the program again. SM0 V 2027 No such position planning table number or the format is incorrect. 1. Check the program, compile the program again, and download the program again. 2. Check the settings of the position planning table. SM0 V 2028 High speed output instruction is being executed.

Only one instruction can be executed at a time. Refer to SR28 for the record of the axis number and rearrange the output control procedures. - V 6004 The IP address filter is set incorrectly. Set the Ethernet parameter for the CPU module in HWCONFIG again. SM1108 X 600D RJ45 port is not connected. Check the connection. SM1100 X 6012 There are devices using the same IP address. 1. Check if there are devices using the same IP address. 2. Check if there is more than 1 DHCP or BOOTP server on the network. SM1101 V 6100 The email connection is busy. Retry the email connection later. This error does not cause the PLC to stop running. Solve the problem by means of the related flag in the program.

SM1113 X 6103 The trigger attachment mode in the email is set incorrectly. Set up the trigger attachment mode in HWCONFIG > CPU Module > Device Setting > Options > Ethernet Port Advanced > Email > Trigger Setting > Trigger Attachment Mode. SM1113 X 6104 The attachment in the email does not exist. Check whether the attachment exists in the memory card. SM1113 X 6105 The attachment in the email is oversized. Check the size of the attachment. If the size is over 2 MB, the file cannot be sent as an attachment. SM1113 X 6106 There is an SMTP server response timeout.

Check for the correct address and set up the SMTP server in HWCONFIG > CPU Module > Device Setting > Options > Ethernet Port Advanced > Email again. SM1113 X 6107 There is an SMTP server response timeout. 1. Check whether the status of the SMTP server is normal. 2. Retry sending of the email later. This error does not cause the PLC to stop running. Solve the problem by means of the related flag in the program. SM1113 X 6108 SMTP verification failed Check for the correct ID/Password and set up in HWCONFIG > CPU Module > Device Setting > Options > Ethernet Port Advanced > Email again. SM1113 X 6200 The remote communication IP address set in the TCP socket function is illegal. 1.

Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG CPU Module > Device Setting > Options > Ethernet Port Advanced > TCP Socket. - X 6201 The local communication port set in the TCP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module - X