Chapter 7 Troubleshooting 7.3 Troubleshooting for Analog Modules Digital I/O, analog I/O, and temperature measurement modules can be installed in a DVP-ES3 Series system. Error status is shown in error codes in CR#43. 0 indicates normal and 1 indicates error. Refer to the following table for more details. 7_ 7-13 Error RUN ERROR LED Description Solution Code LED bit0 OFF ON The external voltage is abnormal. Check the power supply. bit1 RUN: Blinking STOP: OFF Blinking Hardware failure Contact the factory. bit2 Conversion value exceeds the set upper/lower value Check the upper and lower value bit3 The signal received by channel 1 exceeds the range of analog inputs (temperature).
Check the signal received by channel 1 bit4 The signal received by channel 2 exceeds the range of analog inputs (temperature). Check the signal received by channel 2 bit5 The signal received by channel 3 exceeds the range of analog inputs (temperature). Check the signal received by channel 3 bit6 The signal received by channel 4 exceeds the range of analog inputs (temperature). Check the signal received by channel 4 bit7 The signal received by channel 5 exceeds the range of analog inputs (temperature). Check the signal received by channel 5 bit8 The signal received by channel 6 exceeds the range of analog inputs (temperature).
Check the signal received by channel 6 bit9 Mode setting error Check the mode setting bit10 Average time setting error Check the average time setting bit11 Upper/lower value setting error Check the upper/lower value setting bit12 Set value cannot be changed. Check the value in CR#40 (set value changing prohibited) bit13 The later module is disconnected. Check the wiring.