DVP-ES3 Series Programming Manual 7.4 LED Indicators and Error Codes for CPU Modules The error codes and LED indicators are presented in the following tables. Descriptions used in the table a. Error code: If an error occurs in the system, an error code is generated. b. Description: The description of the error c. CPU status: If the error occurs, the CPU stops running, keeps running, or shows the status you defined for the error. Stop: The CPU stops running when the error occurs. Continue: The CPU keeps running when the error occurs. d. LED indicator status: If the error occurs, the LED indicator is ON, OFF, or blinks. ERROR:
System error LED Indicator Description Table There are five types of error indicator states for of the CPU module errors, including LED indicator ON, OFF, blinking fast, blinking normally, and blinking slowly. When the LED indicator is ON, blinking fast/normally, clear the problems first in order to run the CPU module. When the LED indicator is blinking slowly, indicating a warning type of error codes, it does not require immediate action. Clear the problems when the module is powered off. _7 Error Code Description Table 7-14 Module Type LED Indicator Descriptions ON: A serious error occurs in the module. Error Type Blinking fast (every 0.2 seconds):
unstable power supply or hardware Failure. Blinking normally (every 0.5 second): system program errors or system cannot run. CPU Blinking slowly (every one second and off for three seconds): a warning is triggered, but the system can still run. Warning Type OFF: a warning is triggered, but the system can still run. You can modify the rules of how a warning is triggered, or use the SM/SR to show the warnings. ERROR LED indicator status Error CPU Description code status Blinking Blinking Blinking ON OFF fast normally slowly 000A Scan timeout Stop V 000C The program in the PLC is damaged. Stop V 0010 The access to the memory in the CPU is denied. Stop V 0011 The PLC ID is incorrect.
Continue V 0012 The PLC password is incorrect. Continue V 0026 RTC cannot keep track of the current time Continue V 002A 24VDC power supply is not sufficient and then is recovered from low-voltage for less than 10 ms. Continue V