Delta DVP-ES3 — 7.4 LED Indicators and Error Codes for CPU Modules

Chapter 7 Troubleshooting 7_ 7-15 ERROR LED indicator status Error CPU Description code status Blinking Blinking Blinking ON OFF fast normally slowly 002D The PLC maximum password attempts exceeded. Continue V 002E The access to the external memory of the CPU is denied. Stop V 002F PLC programs are not consistent with the system logs. Stop V 0050 The memories in the latched special auxiliary relays are abnormal. Continue V 0051 The latched special data registers are abnormal. Continue V 0052 The memories in the latched auxiliary relays are abnormal. Continue V 0054 The latched counters are abnormal. Continue V 0055 The latched 32-bit counters are abnormal.

Continue V 0056 The latched special auxiliary relay is abnormal. Continue V 0059 The latched data registers are abnormal. Continue V 005D The CPU module does not detect a memory card. Continue V 005E The memory card is initialized incorrectly. Continue V 0063 An error occurs when data is written to the memory card. Continue V 0064 A file in the memory card cannot be read. Continue V 0102 The interrupt number exceeds the range. Stop V 0202 The MC instruction exceeds the range. Stop V 0302 The MCR instruction exceeds the range. Stop V 0D03 The operands used in DHSCS are not used properly. Stop V 0E05 The operands HCXXX used in DCNT are not used properly.

Stop V 1800 - 180F Errors occurred in the extension modules Continue V 1900 - 191C Heartbeat errors occurred in the slave of the Delta ASD-A2 control. Continue V 1950 The initialization of the Delta ASD-A2 control has not yet been completed, the CANopen instructions cannot be executed. Continue V 2001 Not in the right mode for the ASDA-A2 while using the CANopen communication instruction. Continue V 2003 The device used in the program exceeds the device range. Continue V 200A Invalid instruction Stop V 200B The operand n or the other constant operands K/H exceed the range. Continue V 200C The operands overlap. Continue V