Delta DVP-ES3 — 6.19.2 Explanation of Communication Instructions

DVP-ES3 Series Programming Manual 5. See the explanation of the values of ErrCode in the table below. Example 1 Mode=0 Only set1 is used to trigger the DMV detection and receiving of DMV response data. See the sequence control diagram below. En Start1 Shoot1 _6 Ready Com. port Ok       Explanation of the timings:  The DMVSH instruction is enabled.  Set Start1 to On to notify the instruction to send the output signal Shoot1 (ON for about 10ms) and notify DMV to enable the detection function.  After DMV receives the trigger message, Ready is set from On to Off.  Shoot1 is cleared to Off automatically by the PLC.  After DMV detection is finished, Ready is set from Off to On.

The PLC starts to judge if Ready is on after waiting for 1.5 times the input filtering time. The PLC receives the message that Ready changes from Off to On and sends a read command via Modbus 0x03. 6-606 Error code Description Correction 16#0001 The specified communication port is incorrect. Specify a new communication port number. 16#0002 DMV response fault Check the communication address 16#0003 No response from DMV Check if the cable is connected properly or DMV has been enabled. 16#0004 Waiting for the response from DMV; DMV detection cannot be enabled repeatedly. Modify the timing of enabling DMV detection. send receive