Delta DVP-ES3 — 6.20.2 Explanation of Other Instructions

DVP-ES3 Series Programming Manual Example When M0 is ON, the MOV instruction sets the value in D0 is set to 0, and the EPUSH instruction transmits the values in E0–E9 to D1–D10. After the execution of FB0 is complete, the EPOP instruction reads the values in D1–D9 into E0–E9. _6 Additional remarks 1. If the value in D is not in the range 0–100, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If the range of device is not sufficient for D +((the value in D ) *16-1), the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 6-622