Delta DVP-ES3 — 6.20.2 Explanation of Other Instructions

Chapter 6 Applied Instructions Symbol S : System-data reading code D : Starting device where the read system data are stored Explanation 6_ 1. S is the system information reading code and the codes are listed in the following table. 6-623 API Instruction Operand Description 1906 INFO P S,D Reading the system data Device X Y M S T C HC D FR SM SR E K 16# “$” F S  D  BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S   D    Pulse Instruction 16-bit instruction 32-bit instruction ES3 ES3 ─ S code No.

Description Number of consecutive Remark D devices (Number of Words) 0 Reads the serial number of the product 9 ASCII code 1 Reads Ethernet Mac ID 3 Hex value 2 Reads already-power-on time 2 32-bit value, unit: minutes others Reserved 0 The instruction is not executed.