DVP-ES3 Series Programming Manual 3. If you declare the operand D 2 in ISPSoft, the data type is ARRAY [2] of WORD. 4. The following table explains the errors in the execution of the instruction. 5. The following table explains the status codes in D2 [0]. 6-712 Error Code Error Flag Description 16#2003 SM0 / D1 1. Value in S1, S2, S3, or S6 exceeds the range 2.
S+n out of range of the device address 16#200B SM0 Operand n out of range 16#600D SM1100 Ethernet network not connected 16#6301 D1 Connection with remote device broken 16#6302 D1 Remote device response timeout 16#6303 D1 Illegal IP address 16#6304 D1 Error in response command service code 16#6305 D1 Error in response command length 16#6306 D1 Communication conflicts Status Description What to Do Code 16#00 Connection successful 16#01 Connection error Ensure the EDS file of the slave is correct. 16#02 Connected devices unavailable 1. Ensure the number of devices connected to the master does not exceed the limit. 2. Ensure the number of devices connected to the slave does not exceed the limit.
16#03 Error in parameter Ensure the read/written data in S is correct. 16#04 Path error Ensure the settings are correct for Class ID (S4), Instance ID (S5), and Attribute ID (S7). 16#05 Destination path does not exist Ensure the settings are correct for Class ID (S4), Instance ID (S5), and Attribute ID (S7). 6 _