Chapter 6 Applied Instructions 6-713 Status Description What to Do Code 16#07 Connection broken 1. Ensure the Ethernet port of the slave device is connected properly. 2. Ensure the keep alive timer setting is correct for the slave device. 16#08 Service code not supported Ensure the function code (S3) is correct. 16#09 Invalid attribute value Ensure both the registers involved in reading/writing data and their contents are correct. 16#0A Error in attribute list Ensure the slave device object attribute allows PLC to perform the Get Attribute List and Set Attribute List functions. _ _ _ _ 16#0B Transmission conflicts Ensure the service setting is repeated.
16#0C Object status conflicts Ensure the Owner IO connection is established. 16#0D Object existed Ensure the slave supports the defined object. The service does not need to execute if the defined object is supported. 16#0E Attribute not writable Ensure the object attribute supports the write function. 16#0F No privilege to perform service code Ensure the slave device is allowed to perform the service code. 16#10 Device cannot currently perform service Ensure the Owner IO connection is established. 16#11 Size of response data too large Ensure the length of data in the object attribute does not exceed the limit (100 words).
16#12 Data access sequence error when tag is accessed Ensure the data length and the data type are correct. 16#13 Transmitted data too short Ensure the length (n) of read/written data is correct. 16#14 Attribute value unsupported Ensure the Attribute ID switch (S6) and Attribute ID (S7) are correct. 16#15 Transmitted data are too long Ensure the read/written data length (n) is correct. 16#16 Object does not exist Ensure the Class ID (S4) is correct. 6 6 _