Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

DVP-ES3 Series Programming Manual 5. D only allows Y0–Y7 as the output devices. After the instruction is executed, its output function becomes the high-speed output, and the basic instruction output point control is invalid. It is suggested that you do not use the general output function after using the high-speed output function in the program. 6. The ratio of Duty-OFF Time and Duty-ON Time for the pulse output is 1:1. 7. There is no limit to how many times you can use the instruction a program. But only one output instruction that uses the same output point can be executed in the same scan cycle.

When several high-speed pulse output instructions start the same output point in the program, the PLC first performs the output based on the instruction that is executed first. 8. After every high-speed output instruction for every output point is executed, other instruction occupying the same output point can not start until the high-speed output instruction in execution is disabled. 9. When the high-speed output instruction is executed in an interrupt program or is not in the main process, it is suggested that you use the instruction with the auto-reset function when output is completed and the PLC updates the output state in the END instruction. 10.

After the stop flag is set, the PLC stops the output and clears the busy flag only after executing the start instruction a second time and outputting a full pulse. The PLC continues to output pulses when the stop flag is reset and the previously stopped pulse output is not finished. You set and reset the stop flag is set in the program. 11. The high-speed output points and corresponding SM/SR are listed in the following table.

_6 6-764 Output point number Attribute#2 Y0 Y1 Y2 Y3 Y4 Y5 Busy flag R SM460 SM472 SM480 SM492 SM500 SM512 Completion flag#3 R/W SM461 SM473 SM481 SM493 SM501 SM513 Stop flag R/W SM463 SM474 SM483 SM494 SM503 SM514 Output completion auto-reset#4 R/W SM470 SM475 SM490 SM495 SM510 SM515 Present output position#1 (32-bit) R/W SR460 SR461 SR474 SR475 SR480 SR481 SR494 SR495 SR500 SR501 SR514 SR515 Output point number Attribute #2 Y6 Y7 Busy flag R SM520 SM532 Completion flag #3 R/W SM521 SM533 Stop flag R/W SM523 SM534