Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

Chapter 6 Applied Instructions Notes: #1: All present output positions are latched when power is off. #2: R means Read-only registers, and the data in the registers cannot be modified. R/W means the data in the registers can be read and written. #3: It is suggested that you clear the completion flag. If the completion flag is not cleared, it is cleared automatically when the high-speed output instruction is executed the next time. #4: You set the output completion auto-reset flag. The PLC clears the flag automatically after the output is completed. Example 1 1. When M0 is ON, Y0 outputs 200 pulses at 1kHz. SM461 is ON when the pulse output is completed and then M12 is 6_ ON. 2.

When M0 is OFF, Y0 stops the output. It restarts the pulse output when M0 switches to ON again. 0.5ms 200 6-765 Output point number Attribute#2 Y0 Y1 Y2 Y3 Y4 Y5 Output completion auto-reset #4 R/W SM530 SM535 SM550 SM555 SM570 SM575 Present output position #1 (32-bit) R/W SR520 SR521 SR534 SR535 SR540 SR541 SR554 SR555 SR560 SR561 SR574 SR575 輸出 Y0 2 3 Output point Y0 輸出 Y0 Output point Y0