Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

DVP-ES3 Series Programming Manual Symbol S 1 : Target output frequency S 2 : Number of output pulses _6 S 3 : Ramp-up/ down time D : Pulse output device Explanation 1. This instruction specifies the pulse output ( S 1 , S 2 ) for the device specified in D with ramp up or ramp down in the frequency change. S 1 specifies the pulse output frequency between 0 Hz–200 kHz for the open collector output kHz it is about 0.01%. The error rate decreases with decreasing frequency. For example, if the output frequency models. The unit of the output frequency is 1 Hz. The tolerable error rate for 200 kHz is about 0.02% and for 100 setting is 199990 Hz, the actual output is 199960 Hz.

If the output frequency setting is 99999 Hz, the actual output is 99990 Hz. If the output frequency is out of the valid range, the PLC automatically processes it as the maximum or minimum pulse output frequency. 2. After the instruction is executed, you can change the target output frequency specified by S 1 and the PLC performs the ramp up or ramp down process according to the ramp up or ramp down time setting S 3 . The time to change the frequency is when the PLC is scanning the instruction and the instruction has completed output of a full pulse. 3. S 2 is the number of output pulses. The range is between 0–2,147,483,647.

When you set the number of pulses to 0, then the number of pulses is not restricted and pulses are output continuously until the instruction is disabled. 6-768 API Instruction Operand Description 2701 D PLSR S1,S2,S3,D High-speed pulse output (with ramp-up/down process) Device X Y M S T C HC D FR SM SR E K 16# “$” F S1       S2       S3       D  BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1   S2   S3   D  Pulse Instruction 16-bit instruction 32-bit instruction - - ES3