Chapter 6 Applied Instructions 4. After the instruction starts to output pulses, the number of output pulses that S 2 specifies cannot be changed. 5. S 3 sets the ramp-up or ramp down time with the unit of 1ms. The value is effective when the instruction is executed for the first time. If the target frequency specified by S 1 is modified in the ramp-up process, the ramp up or ramp down time is reloaded for execution. But if the target frequency is modified when the output enters the ramp-down process, the instruction ignores the change. 6. D only allows Y0–Y7 as the pulse output devices.
After the instruction is executed, its output function becomes the high-speed output, and the general instruction output point control is invalid. It is suggested that you do not use the general output function after using the high-speed output function in the program. 7. The target output frequency S 1 , number of output pulses S 2 and ramp up/down time S 3 are illustrated in the following graphic. 8. The ratio of Duty-OFF Time and Duty-ON Time for the pulse output is 1:1. 6_ 9. There is no limit to how many times you can use the instruction a program. But only one output instruction that uses the same output point can be executed in the same scan cycle.
When several high-speed pulse output instructions start the same output point in the program, the PLC first performs the output based on the instruction that is executed first. 10. After the high-speed output instruction for one output point is enabled, other instructions that occupy the same output point can not start until the high-speed output instruction in execution is disabled. 11. When the high-speed output instruction is executed in an interrupt program or is not in the main program, it is suggested that you use the instruction with the auto-reset function when the output is completed and the PLC updates the output state in the END instruction. 12.
After the stop flag is set, PLC performs the ramp-down stop; or it immediately stops the output only after the start instruction is executed a second time and outputs a full pulse. 13. Refer to the PLSY instruction (API 2700) for an explanation of the high-speed output points and corresponding SM/SR. 6-769