DVP-ES3 Series Programming Manual Symbol _6 S 1 : Ramp-up time S 2 : Target output frequency S 3 : Ramp-down time D 1 : Pulse output device D 2 : Auxiliary output device Explanation 1. This instruction specifies the JOG output ( S 1 , S 2 , S 3 ) for the devices specified in D 1 and D 2. S 1 is the ramp-up time with the unit of 10 ms. For Example , the value 10 means the ramp-up time is 100 ms. After the instruction is executed, the output frequency can be divided by ten, and it speeds up once every 10ms. It reaches the JOG target frequency specified by S 2 at the ramp-up time S 1 . 2.
When the instruction is disabled, its output frequency ramps down once every 10ms based on the ramp-down time in S 3 . The output does not stop until reaching the ramp-down time. If you set the ramp-down time to 0, the output stops immediately. 3. The range of the ramp-up time S 1 and the ramp-down time S 3 is between 0–3000 (0–30 seconds). If the setting value is out of range, the PLC processes it as the minimum or maximum output value.
The ramp-up time and 6-774 API Instruction Operand Description 2703 D JOG S1,S2,S3,D1,D2 JOG output Device X Y M S T C HC D FR SM SR E K 16# “$” F S1 S2 S3 D1 D2 BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1 S2 S3 D1 D2 Pulse Instruction 16-bit instruction 32-bit instruction - ES3 ES3