DVP-ES3 Series Programming Manual Note: the time source here is from PLC scan time. 8. When the output begins, the Busy flag SM is ON. When the output is completed, the Busy flag is automatically reset to OFF and the Completion flag is not ON. 9. The following graph shows the output timing diagram. For the Busy flag in the following graph, refer to the Busy flag axis. Jog_in Busy flag S 2 > 0 S 1 S 3 D 1 Time 0 S 1 S 3 S 2 10. You can modify the target output frequency during instruction execution. When the new frequency is greater than the previous one, the instruction uses the ramp-up slope. When the new frequency is less than the previous one, _6 the instruction uses the ramp-down slope.
11. The instruction sets the ramp-up/down slope through conversion of the set time and target frequency when the instruction is executed. The slope does not change with the changing target frequency in the output process. For example, the original target output frequency is 1 kHz and then it is modified to 2 kHz. The actual ramp-down time is different from the original time. The dotted line is the ramp-up and ramp down timing diagram after the target frequency is modified. Jog_in Change S 2 S 2 D 1 Time S 1 S 3 Example (ST program): 6-776 Output point for D1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 SR number SR640 SR641 SR642 SR643 SR644 SR645 SR646 SR647