Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

DVP-ES3 Series Programming Manual Symbol _6 S 1 : Target frequency for zero return S 2 : JOG frequency for DOG S 3 : Zero return mode S 4 : Input device for DOG D : Pulse output device Explanation 1. This instruction causes the machine to return to the zero point. The range of the target frequency for zero return S 1 is between 1 Hz–200 kHz. The JOG frequency S 2 should be less than the target frequency S 1 . The JOG frequency S 2 is the start frequency. If S 1 is less than S 2 , S 1 is automatically revised processed as equal to S 2. 2. The input point for S 4 and output point for D must match. Do not change them during instruction execution.

The input point for S 4 is suggested to use the 16 high-speed input points X0–X7 and X10–X17. They will not be affected by PLC instruction scan time. If you use X20 successive input points or M devices, they will be affected by the PLC instruction scan time. Refer to the following table for the selection of D output point and direction output point. If D is not the preset Pulse+direction output (default: 0), change the mode to A/B phase output by setting SR to 1.

6-778 API Instruction Operand Description 2704 D ZRN S1,S2,S3,S4,D Zero return Device X Y M S T C HC D FR SM SR E K 16# “$” F S1       S2       S3       S4  D  BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1   S2   S3   S4  D  Pulse Instruction 16-bit instruction 32-bit instruction - - ES3