2 Functions of Devices in DVP-PLC Function Group Output Latched During STOP Number M1033 Contents: When M1033 = On and PLC goes from “RUN” to “STOP”, the On/Off status of output will be retained. Assume the output contact load of the PLC is a heater, when PLC switches from RUN to STOP, the status of the heater will be retained. After the PLC program is modified, the PLC will RUN again. Function Group All Output Y Inhibited Number M1034 Contents: When M1034 = On, all Y outputs will turn “Off”. M1034 all outputs inhibited Function Group RUN/STOP Switch Number M1035, D1035 Contents: 1.
When M1035 = On, EH2/SVEH3/SV2 series MPU will determine the content (K0 ~ K15) in D1035 to enable input points X0 ~ X17 as the RUN/STOP switch. 2. When M1035 = On, SA/SX/SC series MPU will enable the input point X7 (in SA), X3 (in SX) and X5 (in SC) as the RUN/STOP switch. Function Group Detecting Speed of X0 ~ X5 Number M1036 Contents: 1. For SC_V1.4 and versions above, SPD can detect the speed of X0 ~ X5 at the same time. The total bandwidth is 40kHz. 2. Program example: X7 DVP-PLC Application Manual 2-78 Device No.
Cleared Device M1032 Contact status of M and S for latched Contact and timing coil of accumulative timer T Contac and timing coil of high-speed counter C for latched Present value register of D for latched Present value register of accumulative timer T Present value register of high-speed counter C for latched 7 SET M1036 SPD X1 K1000 D0